Enter your room dimensions and air changes per hour to get the exact airflow your exhaust fan must deliver.
Quick answer: Exhaust fan size depends on room volume and air changes per hour, not floor area alone. Use CFM = length × width × height × ACH ÷ 60; a typical bathroom uses 8 ACH, so a 10 × 10 × 8 ft room needs about 107 CFM before adding a 10–20% duct-loss margin. Convert CFM to m³/h by multiplying by 1.699, then select a fan that still meets the target at its working pressure.
Results are a minimum sizing guide — add a 10–20% margin for duct bends, filters and long runs.
Prefer watching? The 90-second version of this guide — more sizing videos on our YouTube channel.
CFM (cubic feet per minute) is the amount of air an exhaust fan moves in one minute. In metric markets — the Middle East, Europe and Australia — the same figure is usually quoted as m³/h (cubic metres per hour). Both measure the same thing: how fast the fan can replace the air in a room.
The single biggest reason an exhaust fan "doesn't work" is that it was sized for the room's floor area instead of its volume and the air changes per hour (ACH) the application requires. A 50 CFM fan that is adequate for a small bathroom will do almost nothing in a 500 m³ restaurant kitchen.
For metric: m³/h = Room volume (m³) × ACH. To convert, 1 CFM ≈ 1.699 m³/h.
| Application | Recommended ACH | Typical fan type |
|---|---|---|
| Bathroom / toilet | 8 | Ceiling or window exhaust fan |
| Residential kitchen | 15 | Wall or window exhaust fan |
| Commercial kitchen | 20 | High-pressure inline or centrifugal fan |
| Warehouse / storage | 6 | Wall shutter or axial fan |
| Workshop / garage | 10 | Wall or inline duct fan |
| Office / meeting room | 6 | Silent inline or ceiling fan |
A bathroom measuring 10 ft × 8 ft × 8 ft (volume 640 ft³) needs 8 air changes per hour:
You would select a fan rated at least 90–100 CFM after adding a small margin for the duct run.
The chart applies the formula at 8 ACH with a standard 2.4 m (8 ft) ceiling, so you can skip the maths for the most common room sizes:
| Bathroom size | Volume (ft³) | Required CFM (8 ACH) | Suggested model |
|---|---|---|---|
| 5 × 8 ft (4 m²) | 320 | ~45 CFM (76 m³/h) | KLT-10B 6" |
| 8 × 10 ft (7.4 m²) | 640 | ~85 CFM (144 m³/h) | KLT-10B 6" |
| 10 × 12 ft (11 m²) | 960 | ~130 CFM (221 m³/h) | KLT-12B 8" |
| 12 × 15 ft (16.7 m²) | 1,440 | ~190 CFM (323 m³/h) | KLT-12B 8" |
| 20 × 20 ft commercial washroom (37 m²) | 3,200 | ~430 CFM (731 m³/h) | KLT-20B 12" |
For ducted installations — where the fan is not mounted in the wall itself — pick the model whose airflow still clears the target after duct losses, or step up to a mixed-flow inline fan, whose pressure curve holds up better under resistance.
An axial fan is rated at a specific test pressure, and the number on the datasheet is measured at a set static pressure — often 0 Pa, called free air. The real CFM you get depends on the resistance of your installation:
This is why our product pages list CFM at rated pressure, not just free air — see the exhaust fan range for tested values per model.
For whole-house ventilation the goal is 15–20 air changes per hour in hot climates (a shortcut rule is 30 CFM per 100 sq ft of floor area). Calculate the total volume of the conditioned space, then apply the same formula with a higher ACH:
Example: a 2,000 sq ft house with 9 ft ceilings has a volume of 18,000 ft³, so it needs 4,500 CFM of continuous extract. In practice this is delivered by several fans zoned by area — bathrooms and kitchens on their own controls — rather than one oversized unit. For hot, humid Gulf climates, run the fans continuously at low speed; see our Middle East climate ventilation guide.
The required CFM stays the same — air changes depend on room volume, not where the fan sits. What changes is how much of the rated CFM you actually get:
For commercial projects, consultants increasingly ask for ventilation verification — proof that the installed system delivers the design airflow. A simple commissioning check anyone can run:
BAER can supply factory test curves and test reports for any model on request — useful for consultant-submitted projects and tender documentation.
The calculator on this page is not theoretical — it is the same sizing logic our export team runs when a distributor sends a room list. Four orders from our own shipping records:
| Country | Buyer | Venue | Fan type | Quantity |
|---|---|---|---|---|
| Romania | Lighting contractor | Shopping mall | Mixed-flow inline | 2,000 units |
| Iraq | Trading partner | Commercial kitchens | Mixed-flow inline | 1,000 units |
| Saudi Arabia | Trading partner | Factory workshops | Window-mounted axial | 2,000 units |
| UAE (Dubai) | Trading partner | Commercial kitchens | Window and ceiling mount | 2,500 units |
The pattern matches everything above: long duct runs in malls and kitchens ended up on mixed-flow inline fans, while direct wall or window openings took axial units. Quantities come from our own order records; buyer names stay confidential.
This calculator gives you the airflow target. These guides cover what a calculator cannot see — static pressure, duct resistance and application-specific margins:
Send us your room dimensions and application — our engineers reply with a recommended model and full specifications within one working day.